CONTACTORS TYPE TADN

FIELD DISCHARGE CONTACTORS TYPE TADN FROM 46 TO 6000 AMPS UP TO 1000V

These contactors are made from the combination of the two special executions TDN and TAN, and are fitted as follows:

a) Main contacts, open when the contactor is open, suitable to energize or deenergize the field circuit of generators, motors, synchronous condensers or exciters;
b) Discharge contacts, closed when the contactor is open, suitable to short-circuit, through a proper discharge resistor, the field circuit at the instant preceding the opening of the main contacts. Moreover, when the contactor is closing, the discharge contacts disconnect the field circuit from the discharge resistor, at the instant following the closing of the main contacts. When used for direct-current generators operation, the discharge contacts are adjusted so that they open before the main contacts close and, viceversa, close after the main contacts open;
c) The control circuit is usually of the <<TA>> type with mechanical latch, but can also be of normal type in D.C. as well as in A.C.

The most frequent type of connection, in the case of synchronous generators excited by static exciters, is the one shown in the figured diagram and the characteristics these contactors have to perform are the following.

 

(Table N°14)

General Characteristics Characteristics of the Main Contacts
(2 poles)
Characteristics of Discharge Contacts (1 pole)
TADN
Size

Vn

V' In Vcc I'cc Icc ICC0,5 Ind Iccd Ichd ID 15''
[V] [V] [A] [V] [A] [A] [A] [A] [A] [A] [A]
85 600 700 85 1000 900 800 4000 85 400 2500 1000
125 600 700 125 1000 1200 1000 5000 125 600 3000 1200
190 600 700 190 1000 2000 1500 8000 190 1000 4000 2000
270 750 700 270 1000 3000 2000 15000 270 2500 6000 3000
350 750 700 350 1000 4000 3000 16000 350 3000 7000 3500
550 750 700 550 1000 6000 4000 20000 550 5000 8000 5500
650 750 700 650 1000 7000 5000 20000 650 6000 10000 6500
800 1000 700 800 1000 8000 6000 25000 800 8000 12000 7000
1000 1000 700 1000 1000 10000 8500 25000 1000 10000 15000 8000
1250 1000 700 1250 1000 15000 10000 35000 1250 10000 15000 10000
1600 1000 700 1600 1000 20000 15000 50000 - - - -
2000 1000 700 2000 1000 20000 15000 60000 - - - -
3000 1000 700 3000 1000 20000 15000 80000 - - - -
3200* 1200 1500 3200 2000 15000 15000 100000 - - - -
4000* 1200 1500 4000 2000 15000 15000 100000 - - - -
6000* 1200 1500 6000 2000 15000 15000 100000 - - - -

*Version FSS with double interruption on each main pole
- For higher voltage please ask our technical department
- For TADN size > 1250, use pole R800 or R1000

BACK NEXT

Electrical Characteristics | Overall Dimensions | Contactors type TAN | Contactors type TDN
Contactors type TADN | Contactors type NF, NFS | Contactors type CN

What are you looking for? | Let us help | 800-523-9194 | request@pc-s.com
What is your Challenge,
Need Description or Goal?
*First & Last Name:  
*E-Mail & Phone:  
*Company:
Address:
*City & State:  
*Zip Code & Country:  
Much appreciated...what engine,
site, or source referred you?
Searched words or other?
 
 

©2003 - 2011 Panel Components & Systems, Inc. | All Rights Reserved | Website Designed by: Computer Doctors Website Design

website statistics