MultiTek 2 Wire Transmitter AC Current Transducer
Specs & Wiring
|
SELECTION GUIDE M700-AL1 2 Wire transmitter, ave. sensing, RMS calibrated. TYPICAL APPLICATIONS The M700 series are 2 wire transmitters. The M700-AL1 converts the A.C. Input current signal to a 4-20mA D.C. Output. The output is directly proportional to the input signal. 2 Wire transmitters like the M700-AL1, obtain the power to operate from the 4-20mA output circuit to which they are connected, and therefore require no separate auxiliary supply. The M700-AL1 is average sensing RMS calibrated current transmitter. 2 Wire transmitters have an advantage over conventional auxiliary powered transducer, because no separate auxiliary is required, savings in the cost of providing a separate auxiliary supply and wiring are made. The above units are used to measure current in energy management systems, switchboards, generator and telemetery controls. Isolation of 4kV is provided between the input and output signal, allowing the output to be fed to conventional analogue meters, digital meters, PLC, and computer systems. ORDERING INFORMATION Product Code Input In Output Options M700-AL1 5A 4-20mA OPTIONS 1. Calibration at temperature other than 23°C |
TECHNICAL SPECIFICATION INPUT Rated value In 1 or 5 Amp C.T. connected 0.5-10 Amp direct connected Working range 10-125% In Rated Frequency 40- 400 Hz Frequency influence 0.005 % / Hz Overload continuous 4 x In Overload for 1 sec. 50 x In Accuracy 0.2% Linearity <0.1% Repeatability ± 0.05% of span Common mode rejection 130dB Input impedance 0.1 Ohm Response time <250mSec 0-90% at full load OUTPUT DC current 4-20mA Drive voltage 24 volts (max. 35 volts) DC volt drop 12 volts dc max. Output load change effect 0.1% up to RL max. Max. loop load (Ohms) V supply - 12V 0.02 ADJUSTMENT Zero ± 1% Span ± 10% ISOLATION Between input & output 4kV RMS 50Hz for 1 minute ENVIRONMENTAL Working temperature 0 to +60 deg C Functional temperature -25 to +70 deg C Storage temperature -55 to +85 deg c (100 ppm / °C) Relative humidity 95% non condensing Class of climate HSE complying with DIN 40040 -3 complying with VDE/VDI3540 WEIGHT & CASE M700-AL1 Approx. 0.2 kg. 55mm case |