MultiTek DC Current Summation Transducer

SELECTION GUIDE
M100-DS1 DC current 1 input
M100-DS2 DC current 2 inputs
M100-DS3 DC current 3 inputs
M100-DS4 DC current 4 inputs

TYPICAL APPLICATIONS
The M100-DS series of summation transducer take up to four inputs and provide an output signal directly proportional to the sum of the inputs. A typical application is the summation of total kW of four separate generating sets e.g. the four individual kW readings are provided by M100-WA4 transducers with 0-1mA output signals. The M100-DS4 summates the four 0-1mA signals and provides a single output signal that is directly proportional the sum of the total kW of all four generators. It is important to note the following when using summation transducers, to ensure the correct reading is obtained :-
The current and voltage ratios must be identical otherwise the subsequent summation

ORDERING INFORMATION
Product Code:Input:Output:Aux:Freq
M100-DS1 1mA 4-20mA 230V 50Hz
TECHNICAL SPECIFICATIONS
INPUT
Rated value In ± 0-1mA...20mA
Voltage drop 20mV
Working range ±125%
Overload continuous 4 x In
Overload continuous 1.5 x Un

OUTPUT
Rated value mA 0-1/5/10/20 & 4-20mA
Load resistance 12/2.4/1.2/0.6 kOhm
Rated value volts 0-5 / 10 & 1-5 V

ADJUSTMENT
Zero ± 2%
Span ± 10%

AUXILIARY
A.C. Voltage 115 / 230 / 400 V (± 25% /
45-65Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20%
/galvanically isolated / <3W)

WEIGHT & CASE SIZE
Approx. 0.4 kg. 55mm case

OPTIONS
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450V
3. Calibration at temperature other than 23°C