MultiTek DC Current or Voltage 1 Input 3 Outputs Transducer
SELECTION GUIDE M100-DM3 One input three outputs TYPICAL APPLICATIONS The M100-DM3 takes 1 DC Input and provides 3 isolated outputs all directly proportional to the input. The outputs can all be of the same D.C. Value or can be different. Typically this product is used to prevent earth loops between measuring devices. For example the M100-DM3 could have its input signal provided by a M100-WA4 watt transducer with 4-20mA output. The 3 outputs from the M100-DM3 could be as follows. Output A = 4-20mA fed to a PLC. Output B = 0-20mA fed to a analogue meter scaled in kW. Output C = 1-5 volt fed to a chart recorder. The isolation between the Input / Output / Case is 1.5kV and the isolation between each output is 500 volts. ORDERING INFORMATION Product Code Input In Output Aux. Freq. Options M100-DM3 1mA A= 1mA 230V 50Hz B=4-20mA C=10V OPTIONS 1. Non standard inputs / outputs only as far as technically acceptable. 2. A.C. Auxiliary in range 57.7 to 450 volts 3. Calibration at temperature other than 23°C |
TECHNICAL SPECIFICATION INPUT Rated value In ± 0-1 / 5 / 10 / 20 & 4-20mA Voltage drop 20mV Rated value Un ±20mV......10V Impedance 100 kOhm / volt Working range ±125% In Overload continuous 4 x In Overload continuous 1.5 x Un OUTPUT Rated value mA 0-1/5/10/20 & 4-20mA Load resistance 10/2/1/0.5 kOhm Rated value volts 0-5 / 10 & 1-5 V ADJUSTMENT Zero ± 2% Span ± 10% AUXILIARY A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65Hz / < 2VA) D.C. Voltage 24 / 48 / 110 V (± 20% / galvanically isolated / <3W) WEIGHT & CASE SIZE Approx. 0.4 kg. 100mm case INSULATION Test voltage 1.5 kV between Input/ Output/Case 500 volt between each output |