MultiTek RTD Temperature Transducer
SELECTION GUIDE M100-RTD RTD temperature measurement TYPICAL APPLICATIONS The M100-RTD monitors the resistance of either 100 Ohm Platinum, or 120 Ohm Nickel. The RTDs resistance increase as the temperature rises, this resistance change is detected by the M100-RTD, which provides an output corresponding to the temperature being measured. The temperature versus resistance values, are provided by the supplier of the RTD used. RTD measurement of temperature is used in large transformers and large motors, to ensure winding temperatures do not rise to a level that would damage the winding. ORDERING INFORMATION Product Code:RTD:Temp:Output:Auxiliary:Frequency M100-RTD Pt 100 0-250°C 5 mA 230V 50Hz OPTIONS 1. Non standard inputs / outputs only as far as technically acceptable. 2. A.C. Auxiliary in range 57.7 to 450 volts 3. Calibration at temperature other than 23°C |
TECHNICAL SPECIFICATION INPUT 2 or 3 wire input Platinum Pt 100 Ohm RTD min. span 20 Ohms ...max. span 200 Ohms Nickel Ni 120 Ohm RTD min. span 24 Ohms....max. span 240 Ohms OUTPUT Rated value mA - 0-1/5/10/20 & 4-20mA Rated value volts - 0-5 / 10 & 1-5 V ACCURACY Class ± 0.5% ADJUSTMENT Zero - ± 2% Span - ± 10% AUXILIARY A.C. Voltage - 115 / 230 / 400 V (± 25% / 45-65 Hz / < 2VA) D.C. Voltage - 24 / 48 / 110 V (± 20% / galvanically isolated / <3W) WEIGHT & CASE SIZE Approx. 0.3 kg. 55mm case NOTE No isolation is provided between input and output |