MultiTek Tap Position Transducer

SELECTION GUIDE
M100-TAP Resistance measurement

TYPICAL APPLICATIONS
The M100-TAP measures the value of resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap position is increased or decreased the value of resistance increases or decrease respectively. The M100-TAP measure the value of this resistance and provides an output proportional to the value of the number of taps selected.
The M100-TAP can also be used to measure variable resistance 2 or 3 wire systems.

ORDERING INFORMATION
Product Code:No. Of Taps Output: Aux.:Frequency
M100-TAP 10 5 mA 230V 50Hz

OPTIONS
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at temperature other than 23°C
TECHNICAL SPECIFICATION
INPUT
Rated range - min. 100 ohms.... max. 20 kOhms
Sensor current - min. 50uA.... max. 10mA
Sensor voltage - <1 Volt
Working range - 0-125% Rn

OUTPUT
Rated value amps - 0-1/5/10/20 & 4-20mA

Rated value volts - 0-5 / 10 & 1-5 V

ADJUSTMENT
Zero - ±2%
Span - ±10%
AUXILIARY
A.C. Voltage - 115 / 230 / 400 V (± 25% /
45-65 Hz / < 2VA)
D.C. Voltage - 24 / 48 / 110 V (± 20% /
galvanically isolated / <3W)

WEIGHT & CASE SIZE
Approx. 0.4 kg. 55 mm case
NOTE No isolation is provided between input and output