MultiTek Tap Position Transducer
SELECTION GUIDE M100-TAP Resistance measurement TYPICAL APPLICATIONS The M100-TAP measures the value of resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap position is increased or decreased the value of resistance increases or decrease respectively. The M100-TAP measure the value of this resistance and provides an output proportional to the value of the number of taps selected. The M100-TAP can also be used to measure variable resistance 2 or 3 wire systems. ORDERING INFORMATION Product Code:No. Of Taps Output: Aux.:Frequency M100-TAP 10 5 mA 230V 50Hz OPTIONS 1. Non standard inputs / outputs only as far as technically acceptable. 2. A.C. Auxiliary in range 57.7 to 450 volts 3. Calibration at temperature other than 23°C |
TECHNICAL SPECIFICATION INPUT Rated range - min. 100 ohms.... max. 20 kOhms Sensor current - min. 50uA.... max. 10mA Sensor voltage - <1 Volt Working range - 0-125% Rn OUTPUT Rated value amps - 0-1/5/10/20 & 4-20mA Rated value volts - 0-5 / 10 & 1-5 V ADJUSTMENT Zero - ±2% Span - ±10% AUXILIARY A.C. Voltage - 115 / 230 / 400 V (± 25% / 45-65 Hz / < 2VA) D.C. Voltage - 24 / 48 / 110 V (± 20% / galvanically isolated / <3W) WEIGHT & CASE SIZE Approx. 0.4 kg. 55 mm case NOTE No isolation is provided between input and output |