INPUT..........TYPE............RANGE AC VOLTS..
M300-VAD.. 0.....600V DC VOLTS.. M300-VD1 ...±
50/60/75/100/150mV DC VOLTS.. M300-VD2 ...± 50mV ..... 1999mV DC
VOLTS ..M300-VD3 ...± 2V.....199.9V DC VOLTS ..M300-VD4 ...±
200V....600V AC AMPS ..M300-AAD.. 1 or 5 AC (0.2 TO 10A) DC AMPS
..M300-AD1 ...± 1 / 5 / 10 / 20mA DC AMPS ..M300-AD2 ...±
100uA..... 199.9uA DC AMPS ..M300-AD3... ± 20mA......10A DC AMPS
..M300-AD4 ...4/20mA FREQUENCY M300-HZD 35Hz..... 199.9Hz
PERFORMANCE IMPENDANCE :-
M300-VAD 10k Ohm/V M300-VD1/2 >100k Ohm/V M300-VD3/4 10k Ohm/V
BURDEN M300-AAD < 2VA M300-AD1/2/3/4 20mV
OVERLOAD Current 4 x continuous 25 x 1 second
Voltage 1.5 x continuous 4 x 1 second Accuracy ± 0.05% of
reading ± 1 digit Resolution 0.05% Linearity ± 1 digit
roll over error ± 2 digits Conversion Dual slope integration CMR
AC 50dB 50 to 60 Hz DC 25 1k Ohm source unbalanced. Normal mode
rejection 25dB 50 to 60Hz
ENVIRONMENTAL Working Temperature 0 to +60 deg
C Function Temperature - 25 to +70 deg C Storage Temperature -55 to +85
deg C Temperature Coefficient 0.01% per deg C Relative Humidity 0-95%
non condensing Warm up time 1 min. Shock 30G in 3 planes |
INSULATION Test Voltage 4kV RMS 50Hz 1
min AUXILIARY AC Voltage 115 or 230 Volts
(± 25%) 45 to 65 Hz. Burden < 2VA DC Voltage 24 / 48 / 110
Volts (± 20%) Galvanic isolation. Burden < 3W
DISPLAY Digits 1999 Full scale Size 14.2mm (o.56") 7
segment red Decimal point Internally selectable Overrange indication
Display "1" or "-1" Update response time < 1 second Polarity
Automatic with (-) indicating negative inputs
ENCLOSURE Standard DIN case 96 x 48 x 94 mm Panel
mount Via retaining side brackets and screws Panelcutout 92 + 0.8mm x 45 +
0.8mm Material Black Polycarbonate complying with UL 94 VO
Terminals Screw terminal for 2 x 0.5-3.5mm
Enclosure code IP54 NEMA 12 Weight 0.4kg
GENERAL & SAFETY INSTRUCTIONS
All units built and tested for safety, accuracy, quality and reliability. Units
are delivered fully calibrated, however adjustments to "ZERO" and "SPAN" can be
made by removing the appropriate covers on the rear of the instrument.These
products must be installed by a qualified engineer. VOLTAGE dangerous to human
life may be present at some of the terminals of this unit. Exercise extreme
caution during installation. |