Multitek MultiLed M812 Digital Panel Meter


Specifications
Back to M812

INPUT
Rated Un Direct connected voltages between 57.8 and 600 V.

Standard voltages offered :-
Three phase four wire 63.5/110 V, 69.3 / 120 V, 120 / 208 V, 220/380 V, 230 / 400 V, 240 / 415 V, 277 / 480V
Three phase three wire 110 V, 120 V, 380 V, 400 V, 415 V, 440 V, 480 V

Range 5-120% Un
Burden 0.5VA per phase
Overload 1.5 x Un continuous, 4 x Un for 1 second

Rated In 1 or 5 amp
Range 5-120%
Burden 0.5VA per phase
Overload 4 x In continuous, 50 x In for 1 second
Frequency 50 / 60 Hz nominal range 45/65Hz

SYSTEMS
Single phase
Single phase 3 wire
3 phase 3 wire unbalanced load
3 phase 4 wire unbalanced load

ACCURACY
Volt 0.5% of reading ± 2 digit
Amps 0.5% of reading ± 2 digit
Frequency 0.1Hz ± 1 digit
PowerFactor 1% of reading ± 2 digit
Active Power 1% of reading ± 2 digit
Reactive Power 1% of reading ± 2 digit
Active Energy 1% of reading (IEC 1036)
Reactive Energy 1% of reading (IEC 1036)
Apparent power 1% of reading ± 2 digit
Demands 1% of reading ±2 digit
THD 1.5% of range V and I

APPLIED STANDARDS
General IEC 688 BSEN60688, BS4889, IEC 359
EMC Emissions BSEN50081/2
Immunity BSEN50082/2
Safety IEC 1010, BSEN601010

INSULATION
Test Voltage 3 kV RMS 50 Hz for 1 min between inputs / case / relay output. ( 2.5kV between RS232 output / inputs / case /relay )
Impulse Test EMC 5kV transient comply with IEC 801 / EN 55020
HF interference EHF 2.5 kV 1 MHz comply with IEC 255-4
Protection Class II complying with IEC348 / BS4753 / DIN 57411 / VDE 0411

AUXILIARY
ACVoltage 115 / 230 / 400 volts (± 15% ) 45 to 65 Hz.
Burden < 7 VA

DISPLAY
Display: Red LED (software adjustable brightness) Digits: 3 lines x 4 digits
Digit Size: 7 Segment - 14.2mm high
PARAMETERS DISPLAYED
Volts L1-L2,L2-L3,L1-L3 (3 ph 3 & 4 wire)
L1-N,L2-N,L3-N (1 ph & 3ph 4wire)
Amps-L1,L2,L3

Frequency-System frequency
PowerFactor-P.F. of system.
Active power-total real power of system. (W, kW, MW)
Reactive power-total reactive power of system. (VAr, kVAr, MVAr)
Active energy-total kW.h of system. (kW.h)
Reactive energy-total kVAr.h of system (kVAr.h)
Apparent power-total VA of system (VA, kVA, MVA)
Demands - Amps, Watts and VA of system
Peak Demand - Amps, Watts and VA of system
THD voltages and currents

RELAY
kW.h pulse output, normally open volt free contact 50V 150mA 5W ac/dc
Pulse rate Standard 1 pulse per W.h or kW.h or MW.h depending on input values.
Pulse duration programmable in steps of 20msec from 20 msec to 200 msec.

ENVIRONMENTAL
Working Temperature 0 to +60 deg C
Function Temperature -5 to + 60 deg C
Storage Temperature -10 to +65 deg C
Temperature Coefficient 0.01% per deg C
Relatively Humidity 0-95% non condensing
Warm up time 1 min.
Shock 30g in 3 planes

ENCLOSURE
Standard DIN case DIN 96 x 96 x 98mm
Panel mount Via 4 corner brackets.
Panel cutout 92 + 0.8mm x 92 + 0.8mm
Material Black Polycarbonate complying with UL 94 VO
Terminals Screw terminal for 2 x 0.5-3.5mm
Weight 0.6kg

OPTION
Pulsed output W.h or VAr.h User programable
DC Auxiliary 12V, 24V, 30V, 48V, 110V, 125V

SERIAL COMMUNICATION
RS 232 or RS 485 output
Baud rate programmable 19200, 9600, 4800, 2400
Parity programmable Odd, even or none
Stop bits programmable 1 or 2
Addresses programmable 1 to 247 (RS485 only)
Transmission distance 15 metres RS 232 Transmission distance 1.2kM RS 485

Connections
RS232 + & --
RS485 + , -- & Sheild (screen)
Note Shield connection on RS485 units only.

CONTROLS
Two front controls for scrolling up or down, through parameters being displayed.
Used for programming.

What are you looking for? | Let us help | 800-523-9194 | request@pc-s.com
What is your Challenge,
Need Description or Goal?
*First & Last Name:  
*E-Mail & Phone:  
*Company:
Address:
*City & State:  
*Zip Code & Country:  
Much appreciated...what engine,
site, or source referred you?
Searched words or other?