MultiTek Thermocouple Trip Relay
SELECTION GUIDE M200-TJU J type thermocouple under trip M200-TJO J type thermocouple over trip M200-TKU K type thermocouple under trip M200-TKO K type thermocouple over trip TYPICAL APPLICATIONS Designed to monitor thermocouples and provide a relay signal if the temperature being monitored exceeds the pre- set limit. J and K type thermocouples inputs are available covering a wide range of temperatures. As is common with all the M200 relays, on over units the relay energises when the input signal exceeds the trip point and on under units the relay de-energises when the input signal goes below the trip point. A red LED indicates the state of the relay, whilst a green LED indicates the condition of the power supply. ORDERING INFORMATION Product Code Temp range Aux Freq Options M200-TJO 0-300ºC 120V 60Hz 0-30 sec T/D OPTIONS 1. Adjustable time delay max 30 seconds 2. AC auxiliary in the range 57.7 to 480 volts 3. Calibration at temperature other than 23º C |
TECHNICAL SPECIFICATION INPUT Type J Fe/const Min range 0-185ºC (min span 10mV) Max range 0-870ºC (max span 50mV) Type K NiCr/NiAl Min range 0-245ºC (min span 10mV) Max range 0-1230ºC (max span 50mV) Thermocouple break protection Upscale energise Cold junction Compensation Automatic over range 0-50 C Overload 10 x Input continuous SETPOINT Range Over Adjustable 40% to 120% for both voltage and current input Range Under Adjustable 0% to 80% for both voltage and current input Repeatability Better than 0.5% of full span Time delay Adjustable 200ms to 10 seconds Differential Fixed 2% AUXILIARY AC Voltage 115/230/400V ± 25% / 45-65Hz / 2VA DC Voltage 24 volt (± 20% / galvanically isolated) <3 Watt WEIGHT & CASE SIZE Approx. 0.4kg 55mm case |