MultiTek AC Voltage Relay

SELECTION GUIDE
M200-V1U Single phase under voltage
M200-V1O Single phase over voltage
M200-V1C Single phase combined voltage
M200-V33U 3 phase 3 wire under voltage
M200-V33O 3 phase 3 wire over voltage
M200-V33C 3 phase 3 wire combined
M200-V34U 3 phase 4 wire under voltage M200-V34O 3 phase 4 wire over voltage
M200-V34C 3 phase 4 wire combined voltage

TYPICAL APPLICATIONS
The M200 AC voltage relay provides voltage monitoring and protection in both single and 3 phase systems. Used in applications such as mains failure, regulation of power supplies and to protect voltage sensitive equipment.
Under, over and combined under/over units are available. The relay operates when the externally adjustable trip point is reached. An external differential control is provided with adjustment 1-15%. The differential ensures that the parameter being measured returns to % set above or below (depending on whether it is under or over unit) the trip point before the relay returns to its original state.
As is common with al/the M200 relays; on over units the relay energises when the input signal exceeds the trip point. On under units the relay de-energises when the input signal goes below the trip point.
A red LED indicates the state of the relay, whilst a green LED indicates the condition of the power supply.

ORDERING INFORMATION
Product Code Input Freq Options
M200-V34U/D 230V 50Hz 5 sec t/d
TECHNICAL SPECIFICATION
INPUT
Rated value Un Single phase 57.8 <500 V
Three phase 100 <500 V
Frequency 50/60/400 Hz
Burden <2.5 VA per phase single units
<3 VA per phase combined units
Overload 1.5x Un continuous 2 x Un for 3 seconds

SETPOINT
Range under Adjustable 75% to 100% Un
Range over Adjustable 100% to 125% Un
Repeatability Better than 0.5% of full span
Differential Adjustable 1 to 15%
Operating time Typically 200ms

AUXILIARY
All units self powered.

WEIGHT& CASE SIZE
Single units Approx. 0.4kg. 55mm case
Combined units Approx. 0.6kg. 100 mm case

OPTIONS
1. On all of the above units, except the combined, an internally set time delay is available for any value between 1 & 10 seconds. To order use the above codes adding a D at the end of the code, e.g. M200-V34U/D 5 seconds (state the fixed delay period).
2. To prevent nuisance tripping when there is a slight variation in the voltage supply the following option is available. The external differential is replaced on the following products with an externally adjustable time delay. On these units the time delay is adjustable from 200ms to 10 seconds, and the differential is fixed at 1%.
M200- V1X Single phase under voltage
M200-V1Y Single phase over voltage
M200-V1W Single phase combined voltage M200-V33X 3 phase 3 wire under voltage
M200- V33Y 3 phase 3 wire over voltage
M200-V33W 3 phase 3 wire combined voltage
M200-V34X 3 phase 4 wire under voltage
M200- V34Y 3 phase 4 wire over voltage
M200- V34W 3 phase 4 wire combined voltage
3. Calibration at temperatures other than 23º C

What are you looking for? | Let us help | 800-523-9194 | request@pc-s.com