INPUT Rated Un Direct connected
voltages between 57.8 and 600V Standard voltages offered: 3 phase
4 wire: 63.5/110V, 69.3/120V, 120/208V, 220/380V, 230/400V, 240/415V,
277/480V 3 phase 3 wire: 110V, 120V, 380V, 400V, 415V, 440V,
480V Accuracy
Range 20-120% Un
Burden
0.5VA per phase
Overload
1.5 x Un continuous 4 x Un for 1 second
Rated In
1 or 5A Working Range
20-120% Burden
0.5VA per phase Overload
4 x In continuous, 50 x In for 1 second Frequency
45/65Hz (nominal) SYSTEMS Single phase
Single phase 3 wire 3 phase 3 wire unbalanced load 3 phase 4 wire
unbalanced load ACCURACY Volt
0.5% of reading ± 2 digits Amps
0.5% of reading ± 2 digits Frequency
0.1Hz ± 1 digit Power Factor
1% of reading ± 2 digits Active Power
1% of reading ± 2 digits Reactive Power
1% of reading ± 2
digits Active Energy
1% of
reading (IEC 1036) Reactive Energy
1% of reading (IEC 1036)
Apparent Power 1% of reading
± 2 digits Demands
1% of reading ± 2 digits AUXILIARY AC
Voltage 115V / 230V / 400V (± 15%) 45 to 65 Hz burden < 7
VA APPLIED STANDARDS
General
IEC 688 BSEN60688, BS4889, IEC 359 EMC Emissions
BSEN50081/2
Immunity
BSEN50082/2 Safety
IEC 1010, BSEN601010 INSULATION Test Voltage
3 kV RMS 50Hz for 1 min between inputs / case / relay output ( 2.5kV
between RS232 output / inputs / case / relay ) Impulse Test EMC
5kV transient comply with IEC 801 / EN 55020HF
Surge Withstand IEC 801 / EN55020 / ANSI C37.90A
Interference EHF 2.5 kV 1 MHz comply with IEC 255-4
Protection Class II complying with IEC348 / BS4753 / DIN 57411 / VDE
0411
APPROVALS UL, C-UL,
CSA
DISPLAY LCD Custom 6 digit plus
parameter displayed 7mm high characters Characters black, green
backlighting |
CONTROLS Two front controls for
scrolling up or down, through parameters being displayed. Used for
programming
PARAMETERS DISPLAYED Phase and Line
Volts (V) 3 phase 3 wire and 3 phase 4 wire: L-1-L2, L2-L3, L1-L3
Single phase and 3 phase 4 wire (wye connection): L1-N,
L2-N, L3-N Phase Amps (I) L1, L2, L3
Frequency
(Hz)
PowerFactor (PF) Active Power (W, kW, MW) Reactive
Power (VAr, kVAr, MVAr) Active Energy (kW.h) Reactive
Energy (kVAr.h) Apparent Power (VA, kVA, MVA) Amp
Demand Active Power Demand (Watt Demand) Apparent Power Demand (VA
Demand)
RELAY W.h. or
VAr.h
SPNO (normally open volt-free contacts) Rated 50V Pulsed
Output
150mA, 5W AC/DC Pulse
Rate
Automatically set Pulse Duration
Programmable in
steps of 20 msec Range from 20 msec to 200 msec
ENVIRONMENTAL Temperature Ranges: Working
0 to +50 deg C / +32 to 122
deg F Function -5 to
+60 deg C / +23 to 140 deg F
Storage -10
to +65 deg C / +14 to 149 deg F Temp. Coefficient
0.01% per deg C Relative Humidity
0-95% non-condensing Warm up time
1 min.
Shock
30g in 3 planes ENCLOSURE Standard DIN case
DIN 96 x 96 x 98mm Panel mount
via 4 corner brackets Panel cutout
92 + 0.8mm x 92 + 0.8mm Material
Black Polycarbonate (complies with UL 94 VO) Terminals
Screw terminal for 2 x 0.5-3.5mm Weight
0.6 kg / 1.32 lbs. OPTIONS
Pulsed output
W.h or
VAr.h (M802-MD* only) User programmable DC Auxiliary
12V, 24V, 30V, 48V, 110V, 125V
COMMUNICATION
Output
RS232 RS485 (MODBUS) Baud Rate
19200, 9600, 4800, 2400 (programmable) Parity
Odd, even or none (programmable) Stop bits
1 or 2 (programmable) Addresses
1 to 247 (programmable) (RS485 only) Transmission distance RS232: 15
meters RS485: 1.2kM Connections RS232
+ & -- RS485
+ , -- & Shield (screen) Note: Shield connection on RS485
units only |