Multitek MultiGen M820 Generator Monitor


Specifications
Back to M820

INPUT
Rated Un
Directly connected voltages between 57.8 and 600V.
Standard voltages offered :-
3 phase 4 wire and single phase -
63.5/110V, 69.3/120V, 120/208V, 220/380V, 230/400V, 240/415V, 277/480V
3 phase 3 wire -
110V, 120V, 380V, 400V, 415V, 440V, 480V, 600V
Accuracy Range - 20-120% Un Working Range - 5-125% Un
Burden - <0.5VA per phase
Overload
1.5 x Un continuous
4 x Un for 1 second

Rated In
1 or 5 amp
Accuracy Range - 20-120% In
Working Range - 5-125% In
Burden - <0.5VA per phase
Overload
4 x In continuous
50 x In for 1 second

Frequency - 50-60Hz nominal range 45-65Hz
DC volts - 10-30V
Hours Run - Updated every 2 minutes

SYSTEMS
Single phase
3 phase 3 wire unbalanced load
3 phase 4 wire unbalanced load

ACCURACY
Volts - 0.5% of reading ± 2 digits
Amps - 0.5% of reading ± 2 digits
Frequency - 0.1Hz ± 1 digit
Coolant temperature - 1% of reading ± 2 digits
Oil Pressure - 1% of reading ± 2 digits
Hours Run - 1% of reading ± 2 digits
Volts DC 1% of reading ± 2 digits

APPLIED STANDARDS
General IEC 688 BSEN60688, BS4889, IEC 359
EMC Emissions BSEN50081/2 BSEN55022 1995 Class A
EMC Immunity BSEN50082/2
Safety IEC 1010, BSEN601010

APPROVALS
UL, C-UL, CSA Pending

INSULATION
Test Voltage 4kV RMS 50Hz for 1 min between inputs / case / relay output. ( 2.5kV between RS232 output / inputs / case / relay )
Impulse, 5kV transient complying with IEC 801 / EN 55020
HF interference EHF 2.5 kV 1 MHz complying with IEC 255-4
Protection Class II complying with IEC348 / BS4753 / DIN 57411 / VDE 0411
PARAMETERS DISPLAYED
Voltage
3 phase 3 & 4 wire L1-L2,L2-L3,L1-L3
Single phase & 3 phase 4 wire L1-N,L2-N,L3-N
Current
L1,L2,L3
Frequency
System frequency L1-N or L1-L3
Coolant temperature (deg F or deg C)
Oil pressure (bar or psi)
Hours run (run time) DC volts (battery volts)

PROGRAMMING
Multigens are pre-programmed by the factory to the user’s specification. On installation the voltage and current inputs, sender inputs and sender set-points can be reprogramed if necessary. Programming can be accomplished via the front panel buttons or the RS485 port (Modbus protocol). For programming through the RS485 port, a setup program is available.

AUXILIARY
AC Voltage
110/230/400V (± 15% )
45 to 65 Hz. burden < 7 VA

OPTIONS
DC Auxiliary voltage
12/24/48/110/125V burden <7 VA

COMMUNICATION
RS485 / Modbus protocol

Relay Outputs
1 single pole N/C for pressure
1 single pole N/O for temp
Rating AC 250V 7A non resistive 1750VA
Rating DC 30V 7A resistive 210 watts

ENVIRONMENTAL
Working Temperature 0 to +50 deg C
Function Temperature -5 to + 60 deg C
Storage Temperature -10 to +65 deg C
Temperature Coefficient 0.01% per deg C
Relatively Humidity 0-95% non condensing
Warm up time 1 min.
Shock 10g in 3 planes

ENCLOSURE
Standard DIN case DIN 96 x 96 x 98mm, panel mounted using 4 corner brackets and thumb tensioning screws.
Panel cut-out - 92 + 0.8mm x 92 + 0.8mm
Material - Black Polycarbonate complying with UL 94 VO
Terminals - Screw terminal for 2 x 0.5-3.5mm
Weight - 0.8kg (1.75lb)