CONTACTORS TYPE TDN

CHANGE-OVER CONTACTORS TDN FROM 46 TO 4000 AMPS, 1000V A.C. & D.C.

A standard contactor can be fitted with normally open poles (poles open when the contactors is deenergized) and also with normally closed poles assembled on the same axle.

1

The extreme operational conditions which can be obtained with a continuous adjustability, are the following:

a) when closing the contactor, the N/C pole <<R>> opens before the closing of the normal pole <<N>> and, viceversa, when opening, <<N>> opens before <<R>> closes (type of adjustment suitable for the change-over contactors);
b) when closing the contactor, the pole <<R>> opens after closing of the pole <<N>> and, viceversa when opening, <<R>> closes before <<N>> opens (type of adjustment suitable for the field discharge contactors).

As already mantioned, the main characteristic is the possibility of passing from one to the other of the two extreme setting conditions with no-step, even adjusting within large limits the change-over time, or the delay of one pole in respect of the other.

The poles type <<R>> are produced in standard sizes with rating up to 1000 Amps; for higher ratings poles of the existing sizes have to be connected in parallel.

It is also remarkable that the poles <<R>>, besides with poles <<N>> of the same size, can be combined with poles of different sizes as indicated in the table below. Of course the same combinations can also be made with only poles <<R>> or only poles <<N>> of different sizes.

The poles type <<R>> have the same overall dimensions of the poles <<N>> but for the height.

Therefore the overall dimensions of the change-over contactors correspond exactly to those of the normal contactors of the same size and number of poles, except for those indicated in the table below.

Overall Dimensions of N.C. pole (Table N°12)

TYPE

Figured Dimensions [mm]

C D I N O P Q R S T U
R 85 90 105 120 42 - - M6 - 20 48 6,5
R 125 90 115 130 42 - - M6 - 20 48 8,5
R 190 90 135 150 42 - - M8 - 20 48 8,5
R 270 140 170 195 50 - - M8 - 25 57 8,5
R 350 140 180 200 50 - - M8 - 25 57 8,5
R 550 140 195 230 52 - - M12 - 40 70 13
R 650 150 200 230 52 - - M12 - 40 70 13
R 800 80 295 350 173 110 18 M10 25 50 63 10,5
R 1000 80 295 350 173 110 18 M10 25 50 63 10,5
R 1250 80 295 350 173 110 18 M10 25 50 63 10,5

1

**R46-60 is out of Production

Electrical characteristics of the normally closed poles
(table N°13)

POLE TYPE
R

Rated thermal current

Breaking capacity A.C.
(R.M.S. value, cos =0,5)
[A]
Breaking capacity D.C.
(Time constant L/R = 15 ms)
[A]
Making capacity Possible combination
with poles
N type
[A] 220V 380V 550V 110V 220V 440V 600V [A]
R 85 85 1600 1300 1000 1600 1000 500 400 2500 85-125-190
R 125 125 2000 1600 1250 2000 1250 700 500 3000
R 190 190 2500 2000 1900 2500 1900 900 700 4000
R 270 270 4500 3500 2700 4500 2700 1300 1000 6000 270-350-550-6503
R 350 350 5000 4000 3500 5000 3500 1700 1200 7000
R 550 550 6000 5000 4000 6000 4000 2000 1500 8000
R 650 650 8000 6500 5000 8000 5000 2500 2000 10000
R 800 800 10000 8000 7000 10000 7000 4000 3000 15000 800-3000
R 1000 1000 12000 10000 8000 12000 8000 5000 3500 15000
R 1250 1250 12000 10000 8000 12000 8000 5000 3500 20000
BACK NEXT

What are you looking for? | Let us help | 800-523-9194 | request@pc-s.com
What is your Challenge,
Need Description or Goal?
*First & Last Name:  
*E-Mail & Phone:  
*Company:
Address:
*City & State:  
*Zip Code & Country:  
Much appreciated...what engine,
site, or source referred you?
Searched words or other?
 
 

©2003 - 2011 Panel Components & Systems, Inc. | All Rights Reserved | Website Designed by: Computer Doctors Website Design